442A

Industrial Electrician

Real exam 100 questions · 70 to pass · 4 hours

Practice questions

58 original questions for this trade. Pick the kind of test.

Or drill one section

Study

A 100-question paper, and it is not the construction ticket. Distribution, motors and drives, and process control are where the marks sit. House wiring barely shows up.

The paper is 100 questions. Distribution and service are 23 of them, motors and controls are 21, and process control is 17. Seventy right is a pass. This is not the construction exam with a different cover. House services and kitchen circuits are not where the marks are.

The book is still CSA C22.1:24 when a province puts a book in the room. These drills do not copy it. Open the motor rules, the hazardous-location section, and the high-voltage section, and check the numbers against the edition your letter names. Some sittings are closed-book. Read the letter.

Know the motor numbers cold. Synchronous speed is 120 × frequency ÷ poles. A 1750 r/min nameplate is a four-pole machine with slip, not a six-pole. Conductors follow the code table, then 125%. The overload follows the nameplate: 125% if the service factor is 1.15 or more, otherwise 115%. A drive output is not a place for power-factor capacitors. A 4 mA loop current is zero. A 0 mA loop current is a broken wire.

  1. APerforms common occupational skills

    9 questions, 9 percent

  2. BGenerating, distribution and service systems

    23 questions, 23 percent

  3. CWiring systems

    20 questions, 20 percent

  4. DRotating equipment and control systems

    21 questions, 21 percent

  5. ESignalling and communication systems

    10 questions, 10 percent

  6. FProcess control systems

    17 questions, 17 percent

  • Three-phase current

    I = VA ÷ (1.73 × V)

    Use the winding voltage you are asking about. Lower voltage, higher current.

  • Synchronous speed

    r/min = 120 × Hz ÷ poles

    Nameplate speed is lower. That gap is slip.

  • Slip

    (sync − running) ÷ sync

    A 1750 r/min motor on an 1800 r/min field is about 2.8% slip, not 50%.

  • 4–20 mA

    (mA − 4) ÷ 16

    That fraction is the percent of span. 12 mA is half scale. 0 mA is a broken loop, not zero.

  • Drive bus

    Vdc ≈ 1.35 × Vrms

    About 810 V on a 600 V drive. The capacitors hold it after the motor stops.

  • Motor conductors

    125% of the table full-load current

    The overload follows the nameplate. Those are different numbers on purpose.

Full study guide

Scores

Opening scores.

With your code book

CSA C22.1:24. The electrical code is not a free book, so these questions do not copy the rules. Code search asks which rule it is. Code calculation gives you the numbers and names the rule.