Industrial Electrician
Real exam 100 questions · 70 to pass · 4 hours
Practice questions
58 original questions for this trade. Pick the kind of test.
Or drill one section
Study
A 100-question paper, and it is not the construction ticket. Distribution, motors and drives, and process control are where the marks sit. House wiring barely shows up.
The paper is 100 questions. Distribution and service are 23 of them, motors and controls are 21, and process control is 17. Seventy right is a pass. This is not the construction exam with a different cover. House services and kitchen circuits are not where the marks are.
The book is still CSA C22.1:24 when a province puts a book in the room. These drills do not copy it. Open the motor rules, the hazardous-location section, and the high-voltage section, and check the numbers against the edition your letter names. Some sittings are closed-book. Read the letter.
Know the motor numbers cold. Synchronous speed is 120 × frequency ÷ poles. A 1750 r/min nameplate is a four-pole machine with slip, not a six-pole. Conductors follow the code table, then 125%. The overload follows the nameplate: 125% if the service factor is 1.15 or more, otherwise 115%. A drive output is not a place for power-factor capacitors. A 4 mA loop current is zero. A 0 mA loop current is a broken wire.
APerforms common occupational skills
9 questions, 9 percent
BGenerating, distribution and service systems
23 questions, 23 percent
CWiring systems
20 questions, 20 percent
DRotating equipment and control systems
21 questions, 21 percent
ESignalling and communication systems
10 questions, 10 percent
FProcess control systems
17 questions, 17 percent
Three-phase current
I = VA ÷ (1.73 × V)
Use the winding voltage you are asking about. Lower voltage, higher current.
Synchronous speed
r/min = 120 × Hz ÷ poles
Nameplate speed is lower. That gap is slip.
Slip
(sync − running) ÷ sync
A 1750 r/min motor on an 1800 r/min field is about 2.8% slip, not 50%.
4–20 mA
(mA − 4) ÷ 16
That fraction is the percent of span. 12 mA is half scale. 0 mA is a broken loop, not zero.
Drive bus
Vdc ≈ 1.35 × Vrms
About 810 V on a 600 V drive. The capacitors hold it after the motor stops.
Motor conductors
125% of the table full-load current
The overload follows the nameplate. Those are different numbers on purpose.