Construction Electrician

Real exam 100 questions · 70 to pass · 4 hours

Practice questions

673 original questions for this trade. Pick the kind of test.

Or drill one section

Study

The construction paper is the short one: 100 items. Wiring systems and distribution carry more than half of it. Industrial electrician is a different exam.

The paper is 100 questions and four hours. Wiring systems are 30 of them, distribution and services are 28, and motors are 21. Seventy right is a pass. There is no penalty for a wrong answer, so do not leave a blank. Learn the heavy blocks first.

You do not paste the code book into the site. The code-search and code-calculation drills on this page are written against CSA C22.1:24, the 2024 Canadian Electrical Code, 26th edition. Open the book, find the rule, and answer. The rule text stays in the book. Some provinces still accept the 2021 edition. Saskatchewan’s 2026 sheet says the 2024 book is supplied in the room. British Columbia supplies reference material and does not let you bring your own. Ontario’s 309A sitting is commonly closed-book with on-screen code excerpts. Read the letter that books your exam.

Know these cold, then prove you can find them fast if a book is provided. 14 AWG copper is limited to 15 A, 12 to 20 A, 10 to 30 A. Unmarked terminations use the 60°C column at 100 A or less, and 75°C above that, for the first 1.2 m. A breaker marked 80% holds a continuous load to 80% of its rating. A breaker marked 100% can carry its rating. Motor conductors are 125% of full-load current. The overload follows the nameplate: 125% if the service factor is 1.15 or more, otherwise 115%. Bond the neutral only at the service. A Class A GFCI protects people. An AFCI is for arcing. Three-wire control does not restart after a power loss. Two-wire control does.

Dwelling services use Rule 8-200. Basic load is 5 000 W for the first 90 m² plus 1 000 W for each additional 90 m². A range is 6 000 W up to 12 kW, then 40% of the excess. Take the greater of that itemized load and the flat minimum: 24 kW if the area is 80 m² or more, 14.4 kW if it is smaller. Forgetting the flat minimum is how a 100 A service gets marked as 60 A.

  1. APerforms common occupational skills

    11 questions, 11 percent

  2. BGenerating, distribution and service systems

    28 questions, 28 percent

  3. CWiring systems

    30 questions, 30 percent

  4. DMotors and control systems

    21 questions, 21 percent

  5. ESignalling and communication systems

    10 questions, 10 percent

  • Ohm's law

    V = I × R

    Current is volts ÷ ohms. Resistance is volts ÷ amps.

  • Power

    P = V × I

    Also P = I² × R and P = V² ÷ R.

  • Single-phase full load

    I = VA ÷ V

    Use the voltage of the winding you are asking about.

  • Three-phase power

    P = 1.73 × V × I × PF

    Line voltage and line current. 1.73 stands in for √3.

  • Three-phase current

    I = P ÷ (1.73 × V × PF)

    Forgetting 1.73, or the power factor, is the common miss.

  • Single-phase voltage drop

    VD = 2 × L × I × R

    The 2 is the go and the return. R is ohms per the same unit L is measured in.

  • Percent drop

    % = VD ÷ V × 100

    Branch and feeder limit taught for the exam is 3%. From the service to the load, 5%.

  • Continuous load

    Ampacity basis = load × 1.25

    Then the conductor and the breaker still have to pass their own rules.

  • Termination temperature

    ≤100 A unmarked: 60°C. Above 100 A: 75°C.

    Rule 4-006. The 90°C column is for correction factors, not a free pass at the lug.

  • Bundling

    4–6: ×0.80. 7–9: ×0.70. 10–20: ×0.50.

    Table 5C. Count a neutral only when it carries current as a normal condition.

  • Small copper limits

    14 AWG 15 A. 12 AWG 20 A. 10 AWG 30 A.

    Rule 14-104. Higher table ampacities do not raise these overcurrent caps.

  • Motor overload

    125% if SF ≥ 1.15. Otherwise 115%.

    Of nameplate full-load current. The branch breaker is a separate, higher number.

  • Dwelling minimum

    Greater of itemized load and 24 kW

    24 kW if area is 80 m² or more. 14.4 kW if smaller. 24 000 ÷ 240 = 100 A.

Full study guide

Scores

Opening scores.

With your code book

CSA C22.1:24. The electrical code is not a free book, so these questions do not copy the rules. Code search asks which rule it is. Code calculation gives you the numbers and names the rule.