Electrician's Calculator

The sums behind the code-calculation questions. Ampacity tables stay in your copy of CSA C22.1:24. Where a table is required, type the number from the book. This page does the arithmetic.

System
Metal
Resistance
Target
Volts dropped
9.069 V
Percent
7.557 %
Voltage at the load
110.9 V
Branch or feeder, 3%
Over 3.6 V
Service to the load, 5%
Over 6 V
Against the target
Over 3%
Smallest size within the target
10 AWG

Resistance is 0.01 Ω/m, from 0.020968 ÷ 2.081 mm². Drop = 2 × L × I × R. The 3% and 5% lines are Rule 8-102. Table D3 in the book can give a different ohm value.